cables - What's the rationale behind these warnings about extension cords?


(Disclaimer: I've read the help center and I do understand that this is bordering on off-topic since it's about consumer devices. However I hope that I've managed to make enough on-topic by asking about why it is the way it is, and what is the explanation from an electromagnetic point of view - in other words, what laws of electricity and what practical considerations have gone into these decisions).



I recently bought a power tool and in its manual I found a few peculiar safety rules. I cannot see why they would be there, although reading up more it seems that they are commonplace. My understanding of electricity is limited (just about enough to be dangerous), so I'm hoping to expand it. :)


The rules are:



  • Don't use an extension cord longer than 25m. Considering this is an outdoors tool, this limitation is severely restrictive. The best explanation I've seen is that longer cables would simply have too high of a resistance and the tool wouldn't be able to operate at full power. But this argument doesn't convince me. The tool is rated at 2.4kW, and it's meant to be used with 220V AC power source, which means it uses about 11 amps of current. All the extension cords I've ever come across have at least 16A limitation, so there is quite a reserve still. In addition, the power has to travel much, much further to get to my house, and even after the meter it still takes probably close to those same 25m to get to the power outlet. Why only 25m after the outlet? The resistance of the cables isn't that big, is it?

  • Don't daisy-chain extension cords. I suspect this is a variation of the above - don't exceed 25m; every connection adds additional contact resistance; water in the outdoors connections can be a problem - in general, it just adds risk. However, apart from the water in the contacts, the rest seems to me to be practically negligible. Is there really a significant contact resistance? Assuming that the extension cords are in a good shape.

  • Make sure that the power cord is entirely unrolled. This is another odd one. My suspicion is that it has to do with inductive resistance. But is it really that strong? Wherever I've seen people actually wanting to create an electromagnet, it's pretty much hard work. You need a lot of neat, tightly-wound loops of wire. An extension cord has a lot of insulator around it, spacing the wires pretty far apart, and the loops are very chaotic. In addition, if that was a problem, why do extension cord rollers exist? They're used especially when you need a very long extension cord, and you don't need to unroll them completely every time you want to use them. Solved: OK, I was off the mark. The correct answer (also a separate question) has to do with the wire heating up from being used close to its limits. When coiled together, the temperature can go pretty high and melt the cables. Not fun.



Answer



Let's say you're extension cables are 1 mm² cross-sectional area.




  • The loop resistance is 33.6 mΩ/m.

  • A 25 m cable will have a loop resistance of 840 mΩ.

  • The voltage drop at 11 A will be given by V = IR = 11 x 0.84 = 9.24 V. On a 220 V supply this is a reduction of 4.2%.

  • Power dissipated as heat in the cable is given by P = VI or P = I²R = 11² x 0.84 = 102 W. This is a waste of 4.2% power (as we would expect from the previous calculation).

  • String four cords together for a 100 m run and you'll only get 220 - (9.24 x 4) = 183 V.




The situation is a little more complicated than the calculations above suggest because when you add in the cable resistance the current will reduce too. For a 2.4 kW, 220 V load we can calculate \$ R = \frac {V^2}{P} = \frac {220^2}{2400} = 20.2\ \Omega \$. Add in our 100 m loop cable resistance of 4 x 0.84 Ω and the total resistance is now 23.6 Ω resulting in a max current of only 9.3 A which at 183 V (calculated above) reduces the power to VI = 183 x 9.3 = 1700 W which is only 71% of the rated power. The "square" term in the power equation makes the power loss proportional to the square of the voltage loss.




Now to your questions:




Don't use an extension cord longer than 25m. ... and the tool wouldn't be able to operate at full power. But this argument doesn't convince me.



Be convinced by the maths.



All the extension cords I've ever come across have at least 16A limitation, so there is quite a reserve still.



See if you can find the cross-sectional area for those cables and recalculate.



In addition, the power has to travel much, much further to get to my house, and even after the meter it still takes probably close to those same 25m to get to the power outlet.




Ideally your local transformer will be fairly close to your house and, in Ireland, the connection will be using at least 25 mm² cable. You can get some idea of the source "resistance" to your house by monitoring the voltage while you switch on and off a large load such as an electric oven and all the hobs.



Don't daisy-chain extension cords. ... the rest seems to me to be practically negligible.



It may be tolerable (depending on your load) but it's not negligible.



Is there really a significant contact resistance?



This is usually not a factor.




Make sure that the power cord is entirely unrolled.



Our calculations showed that the power dissipated in the cable is 100 W. With the cable tightly rolled the coil temperature will rise. Imagine you wound the cable around a 100 W filament light bulb: what temperature do you think would be reached? Would it get close to melting the insulation?


enter image description here


Figure 1. Source: Why is it dangerous use a coiled extension cord.



My suspicion is that it has to do with inductive resistance.



The term you are looking for is "impedance" for AC resistance. Actually there will be almost zero inductance as the live and neutral currents are in opposite directions and cancel out. I used this trick in work when I needed to create a test load for a 30 A, 30 V 50 Hz supply. We first wound a coil of 1.5 mm² cable of the correct resistance but it was really hopping when we powered it up. When we unwound it, folded in half and rewound it there was no buzz.



enter image description here


Figure 2. Inductance cancellation. See my answer to the question linked above.



But is it really that strong? ... You need a lot of neat, tightly-wound loops of wire.



Or a high current in a low number of turns.