Friday 17 February 2017

ac - How power meter works for residential buildings?


If power is current times meter shouldn't the overall resistances and inductances and capacitances of my house appliances be known so the power meter could calculate the power. I look at my house as a closed circuit. some people say the amp meter measures the current that is used by the appliances but according to ohm's law I need to know the impedances to measure the current.The voltage is standard 120 rms volts.



Answer




The impedance is just the voltage phasor divided by the current phasor. If you measure both (as energy meters do) then the impedance could be known (it's a complex number in general). The impedance of a pure inductance or pure capacitance load will be imaginary (no real part).


However there is no need to calculate the impedance. The energy (what you pay for) is just the time integral of the instantaneous product of current and voltage. Since the meter measures both current and voltage, that is all that is needed.


In the case of old-school energy meters, it's done cleverly with a motor-like arrangement using eddy currents. Modern electronic energy meters do the calculations digitally after digitizing the current measurement (from a shunt, current transformer or Rogowski coil) and the voltage measurement (from a voltage divider or potential transformer).


No comments:

Post a Comment

arduino - Can I use TI's cc2541 BLE as micro controller to perform operations/ processing instead of ATmega328P AU to save cost?

I am using arduino pro mini (which contains Atmega328p AU ) along with cc2541(HM-10) to process and transfer data over BLE to smartphone. I...