Tuesday 21 January 2020

safety - How is using a transformer for isolation safer than directly connecting to the power grid?


How is using a 1:1 transformer safer than using the mains straight off? Is it because you can limit the current coming from the transformer whereas straight from the mains its not current limited? I fail to see how its "safer" when playing with electricity is dangerous. Could someone please explain why it is considered safer to be isolated by a transformer.



Answer



Without a transformer the live wire is live relative to ground. If you are at "ground" potential then touching the live wire makes you part of the return path.


enter image description here


{This image taken from an excellent discussion here


With a transformer the output voltage is not referenced to ground - see diagram (a) below. There is no "return path" so you could (stupidly) safely touch the "live " conductor and ground and not received a shock.


enter image description here



From The Electricians Guide


I say "stupidly" as, while this arrangement is safer it is not safe unconditionally. This is because, if there is leakage or hard connection from the other side of the transformer to ground then there may still be a return path - as shown in (b) above. In the diagram the return path is shown as either capacitive or direct. If the coupling is capacitive then you may feel a "tickle" or somewhat mild "bite" from the live conductor. If the other conductor is grounded then you are back to the original transformlerless situation. (Capacitive coupling may occur when an appliance body is connected to a conductor but there is no direct connection from body to ground. The body to ground proximity forms a capacitor.)


SO a transformer makes things safer by providing isolation relative to ground. Murphy / circumstance will work to defeat this isoation.


This is why, ideally, an isolating transformer should be used to protect only one item of equipment at a time. With one item a fault in the equipment will propbably not produce a dangerous situation. The transformer has done its job. BUT with N items of equipment - if one has a fault from neutral to case or is wired wrongly this may defeat the transformer such that a second faulty device may then present a hazard to the user. In figure (b) above, the first faulty device provides the link at bottom and the second provides the link at top.




Similarly:


enter image description here


No comments:

Post a Comment

arduino - Can I use TI's cc2541 BLE as micro controller to perform operations/ processing instead of ATmega328P AU to save cost?

I am using arduino pro mini (which contains Atmega328p AU ) along with cc2541(HM-10) to process and transfer data over BLE to smartphone. I...