Tuesday, 18 October 2016

Low voltage power lines - formula for spacing between poles?


What is the distance or separation between pole-pole in a 230 VAC distribution line?


Is there any formula for this, or we can take any distance?



Answer



The spacing between towers is a function of:




  • The type of conductor used.



    This is mainly determined by electrical design objectives (i.e. minimum current-carrying capacity). Environmental parameters also play a part.


    Modern aluminium overhead conductor comes in several different alloy compositions, some optimised for electrical characteristics, others with steel reinforcement-wires for strength, and others specialised for harsh environments (i.e. marine salt spray, near coastlines.)




  • The maximum permissible tension on the conductor.


    This is limited by the tensile strength of the conductor, which has to support the conductor against the downwards force of gravity, and the sideways force of the wind, at the maximum wind speed for the geographic area.


    If you live in cyclone/typhoon/hurricane country, the wind speed can exceed 200 km/h sustained or 278 km/h gusts (Australian Category 5 cyclone.)




  • The maximum conductor sag.



    The conductor's temperature varies depending on the ambient temperature and the load (amperes) being carried by the conductor. As the conductor heats up, it lengthens due to thermal expansion, and the conductor sags closer to the ground.


    The transmission line must be designed to maintain a minimum clearance over the ground, at maximum sag. This is especially important when crossing roadways - if a transmission line sags too close to the road, a vehicle might hit the line as it drives past.




Transmission line design sits at the intersection of electrical engineering, mechanical engineering, civil/structural engineering, and materials science. There is no one "formula" that gives the tower spacing distance. The tower spacing distance is part of the overall transmission line design, and needs to be calculated with respect to many variables.


With that said, for common distribution lines, i.e. the 11kV HV + 415V LV distribution lines around my home-town, I would imagine the local distribution company might have a "typical" design. This might read something like: "8m wooden poles, with 6/1/3.75mm ACSR conductor, 4/3/2.5mm earth wire, tower spacing of 50 metres". Such a design would be conservatively engineered considering the local conditions (heavy salt spray and cyclonic winds, in my home town.) It wouldn't translate around the world.


No comments:

Post a Comment

arduino - Can I use TI's cc2541 BLE as micro controller to perform operations/ processing instead of ATmega328P AU to save cost?

I am using arduino pro mini (which contains Atmega328p AU ) along with cc2541(HM-10) to process and transfer data over BLE to smartphone. I...